The operation of VMX series of motor soft starter

the setting of ramp time, starting torque and ramp type shall meet the motor's operation under full load. The factory settings can meet the motor use and basic protection conditions of most users. If there are special requirements, it can be adjusted appropriately, and the adjustment is often operated by using the digital operation interface, that is, the commonly known "panel" or "operation keyboard"

(I) operation interface

vmx series soft starter control interface includes: 8 high brightness LED, 7 function setting keyboard, 4 seven segment nixie tube display modules. Its functions are listed in the table

table VMX series soft starter digital operation interface function table

keyboard reset clear the trip indication, release the trip relay FN, enter or exit the programming mode, when the upward arrow setting, the function code and function content increment key display, the page up key

right arrow setting, you can select the right display position, when the downward arrow setting, the function code and function content decrease key display, When the page down key

left direction arrow is set, the left display bit read en can be selected to be higher than the 12 Richter value than the actual value ter. Select and store the parameters to be set. Green display light

power on control power indicator at speed motor full speed operation indicator yellow indicator light

shut trip the protection generated to the motor when more than two power poles are short circuited, and the shunt trip auxiliary relay acts. Users can use their contacts to interlock and control the external equipment according to their needs

short SCR thyristor short circuit. When the over current indicator light is on, it indicates that two fault conditions may occur: over current or circuit short circuit 1 In case of overcurrent, d) the overcurrent value and overcurrent trip time of the measurement results and production date of this batch of products can be set in f034 and f035. In case of overcurrent, LED will display

to indicate OCA, OCB or OCC

2 SCA, SCC or SCD will be displayed in case of short circuit, and the short-circuit tripping current value is 10 times the rated current, which cannot be adjusted

section

continued table

yellow indicator light

phase loss when the motor is started or running, one or more phases have faults, over temp radiator overheating causes the soft starter to shut down, and after cooling, it can automatically reset the over load motor after overload and tripping, Before clearing the fault, you must reset the display 88884 bit seven segment nixie tube display module (II) display mode

three display modes: status display mode, programming mode and fault display mode

1. Status display mode

status display mode displays seven messages: motor current (three-phase), thermal overload capacity, grounding current, program timer remaining time and clock controller time

status mode:

[0000.] The first message displayed after power on indicates phase a current

[0000] press the up arrow to display phase B current, and then press the up arrow to display phase C current

[g000] press the up arrow to display, indicating the grounding current

figure status display mode

[h000] press the up arrow to display, indicating thermal overload capacity. For example, h070=70% thermal overload capacity

[0000] press the up arrow to display, indicating the program timer. If the screen flashes, it indicates that the timing time is up

[00.00] press the up arrow to display two values separated by decimal points, indicating the clock controller. If [00.00] is displayed, the clock controller is not activated. It can be set through f080-f080

as shown in the figure, please read the status display

[0120.] Indicates phase a current 120a; According to the arrow above, [0121] these synergistic effects will allow Polaris to accelerate the design, development and manufacture of its high-performance electric vehicle, indicating a phase B current of 121a

note: the decimal point is not displayed when the phase B and C currents are displayed

press the up arrow, [0120] indicates that the c-phase current is 120a; Press the up arrow, [g0002] represents the motor grounding current 2A; Press the up arrow, [h083] indicates that the motor has 83% thermal overload capacity

press the up arrow, [0060] indicates that the program timer has 60min left

press the up arrow, [13.30] means 1:30 p.m

press the up arrow, [0120.] Indicates the current circulating to phase A is 120a

2. Programming mode

enter the programming mode, and the soft starter must be shut down. The parameters of different functions can be viewed or set in the programming mode. Press the [fn] key to enter the programming mode. If you enter the programming mode for the first time, the number [f001] will flash after power on. If the VMX has been set and the power is turned on, the last viewed or changed function will be displayed. Use the arrow keys to change the display

(1) browse programmable functions and parameters

each programmable function can be viewed without changing (parameters can also be viewed without changing in the running state). Each function is preceded by the letter "F". Press the read/enter key to display the parameters

[f001] the letter "F" indicates function; [0000] represents the set value of the current function, and the display may have a decimal point due to the different range of function parameter settings and the minimum increase

as shown in the figure, please read the status display

browse function setting value motor full load current setting, [0000.] Phase A has no current (soft starter stops)

press FN key, [f001] indicates that this is function 001 (motor full load current)

press the read/enter key to browse the F001 parameter, [0306] indicates the motor full load current 306a

press FN to return, [f001] to return to function 001

press FN again to return to the status display mode, [0000.] Phase a current

note: if the password is set, the operator needs to set the parameters according to the password

(2) password protection/parameter locking

figure programming mode

vmx series can select password protection through [f070]. If parameters need to be protected, passwords can be set in [f070]. If pressing re is attractive, the ad/enter key displays [err] indicating that the parameter is locked

(3) change the parameter setting

when the read/enter key is pressed, the function parameters will be displayed, and a digit will flash (usually the rightmost digit). A flashing number indicates that the current number can be changed. Use the up and down direction keys to increase or decrease the value, and use the left and right keys to change the next value to be changed. The value can be adjusted within the adjustment range

figure set motor fla

as shown in the figure, please read out the status display

view function setting parameters, [0000.] Phase A has no current (soft starter stops)

press FN key, [f001] indicates that this is function 001 (motor full load current)

press the read/enter key to browse the F001 parameter, [0048] indicates that the full load current of the motor is 48A, and the number 8 flashes to indicate that it can be changed

press the up arrow to increase the value, [0049] the motor full load current after change

press the left arrow to select the second number to be changed, [0049] number 4 flashes

press the up arrow to increase the value, [0059] the motor full load current after change

press the read/enter key to save the new parameter, [end] flashes to indicate that the new parameter has been saved, and the function number will be displayed after flashing

(4) change the function parameters

you can change the size of function parameters through the up and down arrows

as shown in the figure, please read the status display

change function parameters, [0000.] Phase A has no current (soft starter stops)

press the FN key, [f001] indicates that this is function 001 (motor full load current), and the flashing number 1 indicates that it can be changed

press the up arrow twice, [f003] indicates that this is function 3 (motor starting overload level)

press the read/enter key to view the F003 parameter, [0010] indicates that the motor starting overload level is level 10, and the number 0 on the far right flashes

figure change function parameters

press the up arrow to change parameters, [0015] indicates that the motor starting overload level is level 15, and the number 5 on the far right flashes

press the up arrow again to change the parameters, [0020] indicates that the motor starting overload level is level 20, and the number 0 on the far right flashes

press the read/enter key to save the parameters, [end] end flashes once, indicating that the parameters have been saved, and the screen then displays the function number

(5) save parameters

when the parameter is changed to a predetermined value, press the read/enter key to save the parameter. The screen displays end and changes to function number

note: if the equipment is powered off before pressing the read/enter key, the parameters will not be saved

3. Fault display mode

fault display mode displays fault information, and users can also view fault records. The fault code is three letters, the first two are the English abbreviations of the fault, and the last one is a, C or D. "A" indicates the acceleration phase, "C" indicates the operation class, and "d" indicates the deceleration phase

as shown in the figure, please read the status display

check the fault record, [pla.] Indicates phase failure in acceleration phase, and decimal point indicates recent fault

press the up arrow, [ibc] indicates the phase to phase imbalance during operation

press the up arrow, [olc] indicates overload during operation

press the reset key, [rst] flashes once, indicating that the recent fault has been successfully reset. If it cannot be reset, it will display [inh]

[0000.] Return to the default display surface, indicating that the soft starter can be restarted

fault records are only generated when faults occur. You can use the up and down arrows to view the history records. You can check the failure time and date through f085 to f093

(1) fault reset

after troubleshooting, press the reset key, and the screen will return to the status display mode. Press the [reset] key on the panel to reset the fault. Most faults will reset automatically when the soft starter is powered on again. Unless there is enough time for the thermal overload relay to recover to the ability to restart, it cannot be started

(2) remote reset

most faults will reset automatically when the soft starter is powered on again. A dynamic breaking contact (or button) can be connected to the control circuit of A1 or A2 for remote reset

figure view fault record

(3) automatic reset

vmx series can automatically reset minor faults and overload faults. See the table for the settings of automatic reset for non serious faults and the table for the settings of automatic reset for overloads

table motor rated current, load factor, overload protection function setting

function code function adjustment range factory setting F001 motor full load current factory before starting, Must set

50% ~ 100% of the full load current of the motor 0f002 the load factor of the motor is 1.00 ~ 1.301.0f003 the overload level at startup is 5 ~ 30 levels 10 F004 the overload level at operation is 5 ~ 30 levels 10 F005 overload reset 0= manual 1= automatic

2= overload invalid

0 (manual) F006 ~ f009 standby standby meter system setting

function code function adjustment range factory setting f060 user password setting range: 0 ~ 9990= no password

you can choose one of 1 ~ 999 as the password of the device

0f061 reset factory setting 0= disable 1= clear the thermal trigger and shutdown counter

2= reset all settings to factory setting

0f062-f064 standby standby f065 2000 ~ 2047 Product Factory Date f066 January ~ 12 product Factory date f067 1 ~ 31 Product Factory Date f068 hours 0 ~ 23 Product Factory Date f069 minutes 0 ~ 59 Product Factory Date f070 seconds 0 ~ 59 Product Factory Date f071motortronics revision user read-only f072-f074 standby standby standby (4) locking function

this function, such as the minimum time interval between two starts and the limit of starts per hour, is based on the internal real-time clock (RTC). When the soft starter is powered off, the RTC information is quickly saved, and the timer will automatically update according to the RTC. If the locking time is not up, the soft starter does not